Approved by Alyssa Brand
Revised 7/20
Please visit our website for more information on this topic.
29.1 Policy
29.2 Scope and Applicability
29.3 Roles and Responsibilities
29.4 Definitions
29.5 Required Work Processes
29.6 References
29.7 Appendices
Note:
???????? Denotes a new section
???? Denotes the beginning of changed text within a section
???? Denotes the end of changed text within a section
_____________________
This policy describes the safe handling requirements for persons who work with cryogens or operate cryogenic-liquid-handling systems at Lawrence Berkeley National Laboratory (LBNL). This document is not a substitute for On-the-Job Training (OJT).
A cryogen or cryogenic liquid is defined by the National Institute for Standards and Technology (NIST) as any liquid with a boiling point below 93K (-180°C or -240°F) at 1 atmosphere of pressure. This definition includes liquid nitrogen, liquid argon, liquid helium, liquid hydrogen, and liquid oxygen, among others. This definition does not include, and this policy does not cover, liquid propane, liquid butane, liquid acetylene, or liquefied natural gas (methane).
This document addresses cryogenic safety with a primary focus on and specific examples of the inert cryogenic liquids of liquid nitrogen, liquid helium, and liquid argon. Liquid helium, liquid hydrogen and liquid oxygen present additional hazards above liquid nitrogen and liquid argon. For more information on liquid helium, liquid hydrogen and liquid oxygen, see Appendices B, C and D, respectively.
NOTE: Liquid nitrogen is the most frequently used cryogen at LBNL.
All LBNL employees, visitors, affiliates, and subcontractors who handle cryogens or operate cryogenic-liquid-handling systems at LBNL must follow these guidelines:
A thorough evaluation of the safety of a cryogenic application may require a joint effort involving the Environment, Health & Safety (EHS) Division (Safety Engineering and the EHS Research Support Team) and the Facilities Division (Transportation and Rigging Groups).
Role
Responsibility
Facilities Division
EHS Research Support Team Subject Matter Expert (SME)
Line Managers
Supervisors and Work Leads
Cryogenic Liquid Users
In the event of an emergency, LBNL staff and affiliates must:
The following tables identify the properties of and major hazards associated with the use of inert cryogenic liquids, focusing primarily on liquid nitrogen. The hazard list should not be considered exhaustive.
Hazard
Description
Thermal (low temperature)
Pressurization
Venting
Required vents and pressure-relief devices must be vented to a safe location, which is determined with the following criteria:
Oxygen deficiency/asphyxiation
Cryogenic fluids have large liquid-to-gas expansion ratios:
These ratios mean that any accidental release or overflow of these cryogenic liquids will quickly boil into gas and may create an asphyxiation hazard by displacing the oxygen content of the surrounding area.
Ice buildup
Materials concerns
The low temperature of cryogenic liquids will adversely affect the properties of some materials, resulting in system or vessel failure. The process for selecting materials to construct vessels and piping systems for cryogen handling must consider the behavior of the materials at cryogenic temperatures.
Even when the appropriate materials are selected, thermal stresses can lead to failure in some applications. Joining materials with dissimilar coefficients of expansion can also generate thermal stresses.
All components selected and used in cryogenic liquid systems must be designed and manufactured for such service.
Oxygen enrichment
Liquid nitrogen is cold enough to condense the surrounding air into a liquid form. The concentration of oxygen in this condensed air is enhanced. This condensed “liquid air” can be observed dripping from the outer surfaces of uninsulated/nonvacuum-jacketed lines carrying liquid nitrogen. This “liquid air” will be composed of approximately 50% oxygen and will amplify any combustion/flammable hazards in the surrounding areas.
Lifting, physical
Studies of accident statistics involving cryogenics commonly include back strains or other lifting injuries associated with dewars. Although not specifically cryogenic in nature, this hazard is appropriate to note as a hazard associated with cryogenic applications.
Ionizing radiation fields
Using cryogens in high ionizing radiation fields that can generate ozone or nitrogen oxides may cause a potential explosion hazard when the cryogen condenses quantities of oxygen from the atmosphere. The applicable control measure is to minimize the accumulation of oxygen into the cryogen and to keep containers free of hydrocarbon contamination.
Noise
Transfer or venting of cryogens can generate, in some cases, noise levels that may require hearing protection. Sound levels in excess of 150 dBA have been recorded during routine tank filling. A redesign of the equipment or procedure could also be addressed in these cases.
Other, specific
Other cryogenic liquids present specific hazards in addition to the above concerns. Examples include:
This list is not to be considered exhaustive.
Seek additional guidance from the appropriate division ES&H team for a thorough hazard analysis and safe operation of these systems.
LBNL staff and affiliates must be aware of the possible accident scenarios for the LBNL environment. The following table lists known, common accident scenarios involving cryogen applications.
Potential Accident
Description
Accidental releases (or overflows)
Accidental releases (or overflows) of cryogenic liquid can present hazards and cause property damage, as noted in the hazards discussed above.
Releases into building exhaust systems
Releases into building exhaust systems also can present significant hazards.
Pressure buildup (pressure relief valves, PRVs)
Pressure relief valves (PRVs) are required on cryogenic-liquid piping systems to prevent excess pressure buildup when the liquid is trapped between closed valves.
Back injuries
Back injuries may result from lifting cryogenic-liquid dewars.
Tipping of dewars
Storage dewars may be accidentally tipped over when crossing obstructions, such as door thresholds.
Accidents caused by equipment failure (equipment not designed for cryogenic service)
Cryogenic liquids should only be handled in apparatuses specifically designed for that purpose.
Slips, trips, and falls
Cryogenic liquid containers may condense and/or freeze water from the air and leave water on the floor where workers may slip.
Table A.4 The Effects of Oxygen Deficiency
Further Information
Many of the hazards associated with cryogen use are not unique to cryogens. The following table lists some common hazards and where to find more information:
Before beginning any work with cryogens or cryogen systems, workers must be familiar with the cryogenic equipment and systems they will be using.
Using the Work Planning and Control Activity Manager system, in the Description of Work, activity leads shall identify the cryogen equipment and systems to be used, e.g., low pressure storage dewars, open dewar flasks, cryogen cooled vacuum traps, dry/vapor shippers, cryogen filling stations, etc. The Description of Work may also contain procedural information regarding the use of such equipment. The Activity Lead shall read all manufacturer’s instructions regarding the use of and controls for commercially obtained cryogen equipment, and make available this information to all workers on the Activity. For some cryogen systems, On-the-Job Training (OJT) may be required. It is highly recommended that this OJT requirement be documented in the Controls of the Activity.
Appendix A contains detailed information on some of the most common cryogen systems.
Note: When setting up, installing or designing any cryogen system, appropriate materials must be selected, and appropriate controls must be followed as for pressure systems, outlined in ES&H Manual Chapter 7, Pressure Safety.
Note: There are additional requirements for liquid hydrogen and liquid oxygen systems which are enumerated in Cal/OSHA’s General Industry Safety Orders, Group 20, Articles 138 and 139. All systems to contain or deliver liquid oxygen or liquid hydrogen must comply with these orders.
Table B.1 Responsibilities for working safely with cryogens and cryogen systems
Project Lead/PI
Activity Lead
Worker
An easy-to-use oxygen-deficiency hazard (ODH) calculator has been developed as a screening tool, and can be used in many cases. However, sometimes the complexity of a cryogenic system will require a more in-depth quantitative analysis.
Before work with cryogenic liquids is undertaken, an oxygen-deficiency risk assessment must be conducted. There are two types of risk assessments that may be done:
The ODH assessments will need to address the risk of asphyxiation as well as risks from contact with the cryogenic liquid. Any reasonably foreseeable accidents (i.e., spillage, ice plug, cold burns, etc.) should be taken into account and appropriate contingency plans implemented to deal with such emergencies.
The oxygen-deficiency risk assessment will take into account the location of work and room size. Small or poorly ventilated rooms have a much higher risk of asphyxiation due to oxygen deficiency.
For qualitative assessments of the potential to create an oxygen-deficient atmosphere, the simple ODH calculator will be used. To download the ODH Calculator, go here. For more information about the ODH calculator, see Appendix B. An example of the actual output from the analysis of a laboratory is shown below.
ODH Calculator
If oxygen levels could fall below 19.5% during routine operations, suitable control measures should be implemented, e.g., filling or storing vessels in a ventilated room, installing a permanent oxygen monitor, or using smaller storage vessels. An example of a better-ventilated room will generally include a lab with an active fume hood with at least 25% bypass airflow and an active flow-monitor alarm that is set up so the alarm cannot be disabled by local residents.
Situations in which the ODH Calculator is not suitable for ODH determination:
In these situations a quantitative assessment must be performed.
Examples of acceptable quantitative methods for oxygen-deficiency risk assessment methodology include, but are not limited to, the Fermi Lab ODH methodology. While this is a complex and lengthy approach, it has the advantage of being applicable to any cryogenic liquid system and application, including custom-built systems. If a system cannot be modeled with the qualitative ODH Calculator (section 2 above), contact the Cryogenic Liquids SME for a full quantitative risk-assessment.
The quantitative risk-assessment model will result in a fatality rate per hour for the overall use of the proposed cryogen system. Once the fatality rate (f) has been determined, the operation will be assigned an ODH class according to Table C.1 below, where the Risk [f] (hr-1) represents the probability of a fatality occurring per hour in the room. This model takes into account various failure rates and human error rates for the equipment and plumbing involved, and assumes that no oxygen monitors or other safety measures are in place. A risk of 10-7 represents a 1 in 10,000,000 chance of a fatality per hour, and a risk of 1 would theoretically indicate that anyone who enters the room would certainly die within an hour.
Table C.3 Oxygen-Deficiency Hazard (ODH) Classes
The quantitative risk assessment must be conducted by the Cryogenic Liquids SME.
Once the ODH hazard class has been determined, workplace controls can be put in place to minimize the risks. See Work Process D.
The following chart is intended to give a rough approximation of the limits for cryogen use based on the room size and volume of cryogen stored. This information is not to be used in place of an Oxygen Deficiency Hazard analysis as discussed in sections 1 through 3 above, but is merely intended to allow the reader to get a sense for what is and is not possible for a given space.
Chart C.1 Maximum Pressurized Cryogen Storage with ODH Rating 0
Chart C.1 assumes that the cryogen user will store one pressurized cryogen cylinder in the room, for the purpose of supplying inert gas to some piece of equipment or instrumentation. The calculation allows for the simultaneous storage of one 8L non-pressurized transfer dewar, but does not allow for filling of the transfer dewar from the storage dewar. Filling of a transfer dewar in an enclosed space adds significantly to the oxygen deficiency hazard.
Pressure relief valves, or PRVs, used on cryogenic liquid systems must be compatible with cryogenic temperatures and with the physical and chemical properties of the cryogen they are intended to vent. Most importantly, pressure relief valves must not cease to function in extreme cold temperatures or be subject to failure from ice buildup , and must have the flow capacity to safely vent excess gas without further buildup of pressure inside the system. PRVs must also be designed such that a drastic change in temperature (from room temperature to cryogenic temperature) does not cause them to change the pressure at which they vent. Not all cryogenic rated PRVs are suitable for all cryogenic gases. A PRV that functions just fine with liquid nitrogen may not be compatible with liquid helium or with liquid oxygen. Therefore, users must never replace or repair pressure relief devices on cryogenic systems. If a pressure relief valve fails, the user should contact the manufacturer of the system for repair or replacement.
As described in Work Process A, cryogenic liquids can build up extreme pressures if confined and allowed to warm. Cryogenic systems must be designed such that every isolatable part of the system which could conceivably have cryogenic liquid or gas introduced must have its own pressure relief, in the form of a valve or burst disk with adequate gas flow capacity, to prevent explosion from trapped cryogen.
All cryogenic liquid systems which supply cryogenic liquid or vaporized gas from a cryogenic liquid source shall have a manual shutoff valve which is accessible form the point of use. This manual shutoff valve shall not be located in a hazardous area. If the point of use is immediately near the main cylinder valve, then the main cylinder valve is considered to be a manual shutoff valve for this purpose as long as the valve is readily accessible by anyone operating the system.
Wherever practical, people must be protected from inadvertent contact with cryogens or cryogenically cooled parts of a system. This may be achieved through the use of covers, guards, and/or insulation. Where covering, guarding, or insulating the hazard is impractical, PPE must be utilized. See Work Process E.
Depending on the results of the Oxygen Deficiency Hazard (ODH) risk assessment (see Work Process C), a variety of engineering controls may be required to be implemented to safely handle cryogenic liquids. Table D.1 below lists possible engineering controls based on the Oxygen Deficiency Hazard class. This list is not exhaustive.
Entrances to labs that use cryogens must be posted with cautionary signs labeled with the cryogen icon (see below), as required by LBNL’s Chapter 45 Chemical Hygiene and Safety Plan.
Additionally, for work areas that require significant time to evacuate (e.g., tunnels, caves, and similar areas) and where the potential for oxygen deficiency hazard level is “1” or above, the following signs must be posted at the entrance to the space:
Cryogen bulk filling stations must post a sign with a minimum of the following information:
Additionally, owners of bulk filling stations are highly encouraged to post a sign indicating the responsible persons for arranging cryogen delivery to the bulk station and for training new users to safely dispense cryogen.
Engineered controls should be the primary means of worker protection. Where engineered controls cannot fully mitigate all hazards, workers must wear the appropriate PPE to augment any controls in place.
Certain types of operations may increase the risk of exposure to cryogenic liquids. Selection of appropriate PPE must include careful consideration of the specific system configuration and the potential for exposure to all potential hazards. Examples of this include:
Many other operations are considered low risk, and Table E.1 below summarizes the required PPE for low risk operations.
Table E.1 Summary of PPE Requirements for Low Risk Cryogen Operations
1 Recommended. For a few limited operations, cryogen gloves or long-sleeve shirts/lab coats may not be needed.
2 When using a phase separator between the pressurized LN2 line and the open unpressurized dewar, the risk of a cryogen splash is substantially reduced.
Selection of PPE for Work with Cryogens
The primary function of a face shield is to protect the head and face in case of a splash. A good face shield should have adjustments to fit many head sizes and should provide good coverage of the entire front of the head, including around the sides. Some mechanism to lock the shield in place so that it doesn’t slip down and touch the chest is recommended to improve comfort. The shield should have a sloped top surface to direct splashes away from the top of the head and to prevent splashes from getting behind the shield from above. Even better is a face shield with impact resistance, per ANSI Z87.1, which is indicated by a marking of “Z87+” on the face shield surface, but this is not a requirement. Some models have replaceable clear shields so that when the shield becomes scratched or dirty, it can be replaced without purchasing new headgear.
NOTE: You must still wear safety glasses underneath the face shield.
The following image shows an acceptable use of a face shield to protect against cryogen splashes:
Photo Copyright © Cole-Parmer.
Cryogen gloves should be made of non-porous material and should never be confused with heat resistant gloves. Cryogen gloves used to handle hot objects will likely melt, while heat resistant gloves used for cryogens offer no protection from frostbite or burns and can actually trap cryogen against the skin in the porous material of the glove. Ideally, cryogen gloves will be loose fitting and easy to remove. This feature makes it easy to get the glove off in a hurry if cryogen ever becomes trapped inside the glove against the skin.
Before using cryogen gloves, always inspect them for ripped seams, tears or holes where cryogen could get inside the glove.
NOTE: Cryogen gloves are intended for handling very cold items and to protect against an accidental splash. They are NOT meant to be submerged in a cryogenic liquid.
The following image shows a pair of cryogen gloves:
Long pants/trousers are required during all work with cryogenic liquids; shorts and cropped pants are unacceptable. Furthermore, pants/trousers with cuffs can trap cryogenic liquid in the fold of the cuff and against the skin, increasing the chance of cryogenic burns. Cuffed pants/trousers are not permitted to be worn when handling cryogens. It is also recommended to wear loose-fitting pants/trousers so that any spilled or splashed cryogens will roll off the fabric without transferring significant heat into the skin. Tight jeans or leggings provide less protection against cryogen splashes.
It is increasingly common to wear athletic shoes into the laboratory, which are often designed to keep the feet cool, with webbed mesh tops for air flow. Unfortunately, if the shoes allow airflow, they will also allow cryogen into the shoe through the top in the case of a spill or splash, and are often time consuming to remove. Appropriate shoes for use with cryogenic liquids should cover the entire top of the foot and should be able to at least temporarily repel liquids. Shoes with webbed or mesh tops are not permitted when handling cryogens*.
*Closed toe shoes without mesh tops are required. Shoes with enclosed heel and entirely covered tops are recommended.
LBNL staff and affiliates must complete the required training identified below before performing the indicated work activity or fulfilling the indicated role. Untrained LBNL staff and affiliates may temporarily work under the direct supervision of an appropriately qualified supervisor or work lead if the conditions/limitations of such work are documented (e.g., specific activities and duration) before performing the work.
NOTE: This document is not a substitute for on-the-job training. The Activity Lead for your cryogen-related WPC Activity is the only one who can grant you authorization for any cryogen work.
Depending on the outcome of the hazard assessment, the Cryogens Subject Matter Expert, or SME, may need to verify all designated controls are in place prior to the start of cryogen use. The Principal Investigator will arrange for the verification if one is indicated as part of the planning and assessment process.
The following sections give an overview of good laboratory practice for a variety of operations involving cryogens. However, this document is not a substitute for on-the-job training. Always get the appropriate OJT from your Activity Lead before performing any work.
The main hazard associated with working with dewar flasks is burns from cryogen spills or cryogen-cooled tools. Performing any work with open dewar flasks requires the use of safety glasses with side shields, cryogen gloves†, long pants and closed toe shoes, and a lab coat or long sleeves. A lab coat is recommended as the safer option. The following are good laboratory practices for working with open containers of cryogenic liquid:
Immersing Closed Containers in Cryogenic Liquid:
Submerging closed sample tubes, vials or other containers into a cryogenic liquid bath presents another hazard. If the sample container leaks and allows cryogen inside, then is removed from the cryogen, the container may build up pressure and explode. The leak does not have to be large – as the container is cooled, the air inside it will form a slight vacuum that can pull in cryogenic liquid. Be particularly careful when removing closed containers from cryogenic liquid baths.
The transportation of cryogenic liquids in elevators poses a potential asphyxiation and fire/explosion risk if workers become trapped in an elevator with a container of cryogen.
Pressurized Cryogen Cylinders
Low Pressure Cryogen Dewars
Whenever a cryogenic liquid cylinder or a low pressure dewar is being transported in an elevator without passengers, a chain must be used to rope off the elevator entrance and a clearly visible sign must be posted to warn others not to enter the elevator while the cylinder or dewar is present. Once the cylinder or dewar reaches its destination, the person transporting the dewar or cylinder may remove it from the elevator, take down the chain and sign, and return the elevator to normal service. Contact your building manager to have chains and signs installed in elevators that are used to transport cryogenic liquids.
The minimum concentration of oxygen left in an elevator following a liquid nitrogen spill can be calculated based on the amount of liquid nitrogen spilled and the volume of the elevator. A simplified equation is given below as a quick means to estimate oxygen concentrations in a given elevator.
where C is the final oxygen concentration in percent by volume, L is the amount of liquid nitrogen spilled in liters, and V is the volume of the elevator in cubic feet.
b. Cryogen Transport in Vehicles
Table H.2 Self-Transport of Cryogenic Liquids Guidelines
General Requirements:
SERLNG supply professional and honest service.
Vendors such as Praxair, Airgas, and Matheson Tri-Gas are responsible for the safe delivery and transportation of large cryogen dewars to LBNL users.
Note: Dry/Vapor Shipping Containers are by far the safest way to transport cryogenically frozen samples. These containers may be transported on the LBNL shuttles. Clearly mark the container as a dry shipper before boarding the shuttle. Contact the Cryogens SME for information on where to find and order dry/vapor shippers.
c. Cryogenic Materials Transport Between and Within Buildings
This section is intended for guidance only and is not a substitute for on-the-job training. Each fill station is different, and on-the-job training is required for each individual fill station. Authorization to use one fill station does not authorize a user to operate other fill stations.
Before undertaking any filling operation, the user must know the following information:
*Not all fill stations include a bypass line to precool the lines.
NOTE: Appendix F contains some useful calculations that can be used to assess the risk of asphyxiation when using a fill station indoors.
Skin contact with either cryogenic liquids or with uninsulated materials at cryogenic temperatures can cause rapid burns. Often, burns from direct contact with cryogenic liquids are not accompanied by pain but by a feeling of numbness and cold. The affected area may not hurt until it thaws considerably. Contact with materials at cryogenic temperatures can instantly freeze any water near the surface of the skin and cause it to stick to the cold material, in addition to causing burns, which may tear the flesh when it is removed. The eyes are especially susceptible to cryogenic damage and can suffer irreparable harm from direct contact with a cryogenic liquid splash. Even vapors that are near cryogenic temperatures can damage the eyes.
Large exposures to cryogenic liquid or cryogenically cold vapor may induce hypothermia, wherein a person’s core body temperature drops to dangerous levels. If the body is not warmed, heart and respiratory failure can result, potentially leading to death.
In case of skin contact:
In case of eye contact with cryogen or extremely cold vapor:
In case of hypothermia:
Symptoms of hypothermia include: shivering, dizziness, nausea, fast breathing, confusion, lack of coordination, trouble speaking, fatigue and rapid pulse. In more severe cases, breathing may be slow and shallow and the pulse may be weak.
LBNL staff and affiliates must not:
Small amounts of excess cryogenic liquid from processes may be collected in an approved dewar flask and left to evaporate inside of a fume hood.
Excess cryogenic liquid in a low pressure dewar may be left to evaporate naturally from the lidded dewar, so long as the room is already approved for storage of such a dewar.
NOTE: Even relatively small quantities can damage equipment or facilities and can crack floor tiles, damage water pipes, and damage electrical insulation on wiring. Also, consider the hazard presented by the boil-off gas when any significant quantities of a cryogenic liquid are released. Do not pour cryogenic liquid onto floors, onto surfaces inside fume hoods, into any buckets or containers not approved for cryogenic liquid storage, or into any sinks or drains.
Contact LBNL Waste Management for assistance in determining the best way to dispose of cryogenic liquids.
LBNL staff and affiliates must apply the requirements for pressure safety aspects of a cryogenic-liquid-handling system as stated in the Chapter 7 Pressure Safety.
For LBNL designed and assembled systems, the system owner must compile a data package according to the requirements in Chapter 7 Pressure Safety.
Any significant accidental releases must be reported to the appropriate supervisor or work lead. Notification through an emergency and non-emergency hotline may be appropriate, depending on the severity of the release. Any personnel in the vicinity who could be exposed to the hazards of the release must be notified. A predetermined point of contact, such as the person responsible for ordering the product, could also be useful because the schedule for re-ordering may be affected by large-volume releases.
NOTE: Incidents that are reported to the non-emergency hotline are useful in tracking and analyzing accident and failure scenarios, determining trends, and changing engineering configurations or procedures.
Results of qualitative and quantitative risk assessments will be stored in a database for future reference and for use in establishing Work Planning and Control Activities when required. Risk Assessments conducted in the field by persons other than the SME must be emailed to the Cryogens SME.
Commercial (off-the-shelf) vessels which are intended and engineered for cryogenic service may be used as is, but available owner or operator manuals should be retained for reference as part of the system data package.
Source Requirements Documents
Implementing Documents
ES&H Manual, Chapter 7, Pressure Safety
Related Documents
Table of Contents:
Low Pressure Dewars
Image Copyright Chart Industries, Inc. Used with permission, all rights reserved.
Low pressure dewars are only intended for short-term storage of cryogenic liquids, at maximum several days. They are typically only filled on demand. These systems consist of a vacuum jacketed cryogen reservoir, which is usually made of a silvered glass, with an outer casing of aluminum or steel. A loose fitting plug style cap, usually made mostly of foamed plastic for better insulating properties, is used to allow for the release of boil-off gases so that the pressure inside the dewar does not exceed atmospheric pressure, while also keeping air out to avoid condensation of liquid oxygen. In general, these dewars are small and easy to transport. The smallest can be carried with handles, while the larger models may come with wheels mounted to the bottom, or a small cart or dolly may be needed. The vacuum space around the cryogen reservoir is equipped with a pressure relief valve in case the inner reservoir cracks and allows cryogen into the vacuum space. In that scenario, pressure might build up inside the vacuum space and rupture the dewar, so instead it is safely vented through a relief valve.
It is important to inspect all dewars carefully before use. Check that no corrosion is visible on the outside of the casing. The safety valve should be intact and should not be bypassed or defeated in any way. The plug cap should slide easily into the neck of the dewar and should not seal or become stuck.
During use, the dewar should not form ice on the outside of the aluminum casing or on the cap. If ice does form on the outside of the dewar, it indicates that the dewar may have lost vacuum and may no longer be insulating enough for cryogenic liquid storage. Additionally, if there are cracks in the inner silvered glass reservoir, liquid cryogen may get into the vacuum space and upon warming of the dewar the entire vessel can explode from the expanding cryogen. If the foamed plug portion of the cap breaks off or is removed, then the remaining plastic cap will build up ice due to the lack of insulation between the plastic and the cryogenic reservoir. Without proper insulation, the dewar may be allowing more gas to escape into the room than was accounted for in the initial risk assessment for the use of cryogen in that particular room. In the case of a damaged dewar, it is possible that the cryogen reservoir may shatter violently and unexpectedly due to the large amount of stored energy in the pressure differential created by the vacuum jacket.
If there is any sign of damage or loss of insulation, the dewar must immediately be taken out of service and marked as defective to prevent its further use. Only individuals who are trained, qualified and experienced in the repair of this type of vessel should ever attempt to repair a damaged dewar.
Note: Consumer products such as Thermos® bottles and vacuum flasks are not approved for cryogenic applications. Although the container itself may hold cryogenic liquid in an adequate manner, the lid, even when loosely applied, does not allow for proper venting of boil-off gases and may lead to an explosion of the pressurized vessel. These containers must never be used for cryogenic liquids, even for a short period of time. Before purchasing any dewars or “vacuum flasks” for use with cryogenic liquids, check the specifications or call the manufacturer to confirm that it is intended for cryogenic liquid service.
Dewar Flasks
Images copyright © Day-Impex Ltd. All rights reserved.
These open containers are designed to hold cryogen for relatively short periods of time to accomplish various laboratory operations. Many dewar flasks come with a foam, loose fitting or vented lid that can reduce the evaporation rate of cryogen inside without allowing for the buildup of pressure inside the vessel. Depending on whether there is a lid, the type of lid, and the size of the container, dewar flasks may hold liquid cryogen for anywhere from a few hours to a few days. These units can be used to cool the trap on a vacuum line, dip materials for quick freezing, cool entire reaction vessels, etc. Dewar flasks are made of double-layered glass, evacuated between the layers, with a protective aluminum or steel casing. These are the most fragile of all cryogenic liquid containers, but are unlikely to implode without impact or damage to the glass. However, when they do shatter the process is quite energetic and fragments of glass may be ejected from the top opening of the flask at high speed. Wrapping the dewar flask with plastic or tape with the intention of preventing or mitigating an implosion event has not been proven to be effective at preventing or containing implosion events, but is not known to cause any harm. If the unit is wrapped, the wrapping must not cover the warnings printed on the outside of the flask, or else a new warning label must be printed and affixed to the outside of the unit. Because these units tend to accumulate condensation, the label should be waterproof. A typical warning statement is as follows:
WARNING! Vacuum flask – may shatter unexpectedly, may cause injury. Wear safety glasses.
The risk of implosion cannot be completely mitigated, but there are some practices that can reduce the risk somewhat:
While using the dewar flask, it should not form ice on the outside casing, although condensation is normal. If any damage is evident in the form of cracks, scratches, chips or otherwise, immediately remove the dewar flask from service. Do not attempt to repair a damaged dewar flask.
Note: Consumer products such as Thermos® bottles and vacuum flasks are not approved for cryogenic applications. Although the container itself may hold cryogenic liquid in an adequate manner, the lid, even when loosely applied, does not allow for proper venting of boil-off gases and may lead to an explosion of the pressurized vessel. These containers must never be used for cryogenic liquids, even for a short period of time. Before purchasing any dewars or “vacuum flasks” for use with cryogenic liquids, check the specifications or call the manufacturer to confirm that it is intended for cryogenic liquid service.
Pressurized Cryogenic Liquid Cylinders
These units are intended for longer-term storage of cryogenic liquids, on the order of a few weeks to a few months. They typically operate either at pressures of about 22psig for liquid use, or at higher pressures of 230 or 350psig for gas use. The 22psig cylinders tend to be better insulated and are able to hold cryogenic liquid for a longer period of time, but do not vaporize cryogen at a sufficient rate for significant gas withdrawal. The lower pressure makes withdrawal of liquid cryogen safer than if the cylinder were operating at 230 or 350psig. Attempting to withdraw liquid cryogen from a 230 or 350psig cylinder is potentially very dangerous and highly discouraged. The high pressure cylinders are designed to ensure that the cylinder has an appreciable evaporation rate and sufficient pressure for gas operations, which often require delivery pressures greater than 100psig and/or high flow rates.
The design of cryogenic liquid cylinders is necessarily more complex and robust than the atmospheric pressure dewars (see diagrams above) due to the large pressures involved. When extracting cryogenic liquid from the cylinder, the vapor pressure of the cryogen causes the liquid to flow up through a tube and out the liquid valve. Some cylinders may come with a liquid valve built in, while others may require a tube to be inserted into the cylinder, often called a “stinger”. The cryogenic liquid will be released at high pressure because of the pressure inside the cylinder. Use a lower pressure (22psig) cylinder for liquid service to minimize the risks from high pressure cryogen streams. See Work Processes D, E and H for more information on engineering controls, required PPE, and good laboratory practices.
Gas is extracted through a separate valve, which draws from the headspace of the cylinder, above the liquid level. This gas will be just barely warmer than the boiling point of the cryogenic liquid and still poses a significant hazard for burns and frostbite. The high pressure (230 or 350psig) cylinders are usually preferred for gas use because they can deliver higher flow rates, but for applications which require only low flow rates and low pressures, the low pressure cylinders may be used. In order to achieve even higher flow rates, many cryogen cylinders are equipped with a gas use vaporizer, which directs cryogenic liquid through tubing outside of the normal liquid reservoir to vaporize it for immediate use as a gas (see the diagram above). Where necessary, a cryogen cylinder can also be equipped with a pressure builder to allow the user to manually increase the pressure inside the cylinder for an application that requires it. Conversely, where pressure increases more rapidly due to cryogen evaporation than the gas is used, some cylinders have an economizer installed to direct the excess pressure inside the cylinder to the gas use valve instead of using the gas use vaporizer, reducing the amount of cryogen lost to venting through the pressure relief valve.
Before withdrawing gas from a cryogenic liquid cylinder, it is important to verify that the gas use valve is connected and not the liquid valve.
NOTE: Cryogenic liquid cylinders are only intended to be operated in a fully upright position. Never attempt to operate a tilted cylinder (e.g., while on a cart), and never lay a cryogenic liquid cylinder on its side.
Cryogenic liquid cylinders will always have a pressure gauge, a pressure relief valve and a rupture disk installed to prevent over-pressurization of the cylinder. The pressure relief valve and rupture disk must be able to withstand cryogenic temperatures without losing performance or altering the pressure at which they vent. A vent valve provides another means of reducing the pressure inside the cylinder, but manually.
Before filling a cryogenic liquid cylinder, it is important to inspect the cylinder for damage and to verify that the cylinder is approved and designed for the particular cryogen service. For example, liquid helium, liquid oxygen and liquid hydrogen in particular all have very specific requirements for the design of the cylinders (see Appendices B, C and D); these gases should never be filled into a cylinder that is not of the correct design. Some cryogenic gases are even dangerously incompatible, such as LH2 and LOx – an explosive combination. Most cryogenic liquid cylinders will indicate what type of gas they are meant to hold, either by way of a label with the gas identification, or with a clearly marked tag. Never fill a cryogenic liquid cylinder with a different gas than the one for which it is marked.
Common signs of damage on a cryogenic liquid cylinder include rust or corrosion on any of the parts, dents on the external surfaces, tubing and valves that are bent and should be straight, missing pressure relief valves, a burst rupture disk, or a pressure gauge that reads greater than ambient pressure when the cylinder is empty. Never fill a cylinder which shows any sign of damage. It is also important to watch the cylinder once it is filled for any sign of abnormal operation. When withdrawing large flow rates of gas for prolonged periods of time, some ice formation is normal around the gas valve and fittings and sometimes on the sides of the cylinder. Some ice may also build up on the pressure relief valve if the cylinder is venting frequently. However, any ice buildup that cannot be explained through normal operation of the cylinder may be a sign of a defective cylinder. If any signs of damage are observed, or the cylinder behaves abnormally in any way, take the cylinder out of service immediately and contact the manufacturer of the cylinder or the vendor that supplied it. Only individuals who are trained, qualified and experienced in the repair of this type of vessel should ever attempt to repair a damaged cryogenic liquid cylinder.
In many cases, a vendor such as Praxair, Airgas or Matheson will deliver a cryogenic cylinder pre-filled, and pick up the empty cylinder. The vendor is then responsible for inspecting the cylinders before filling and ensuring safe operation. However, it is still important to watch for any unusual signs during operation of the cylinder, such as abnormal ice build-up. If anything seems abnormal, call the vendor immediately to have them pick up the cylinder, and be sure to inform the vendor that you suspect a defect.
Troubleshooting a Problem Cylinder
Pressure in cylinder is too low
Cylinder vents too frequently
Ice on valves of cylinder
Ice on sides of cylinder
Liquid dripping from any of the valves
Pressure above maximum, but not venting
The most likely cause is that the regulator on the cylinder is out of adjustment or defective – if you have another regulator attached to the gas service valve you can check to see if they agree, but the cylinder should still be taken out of service immediately and either returned to the vendor or else repaired by the manufacturer or a trained, qualified and experienced individual.
Cryogen Filling Stations
Cryogen filling stations are a long-term solution to frequent cryogenic liquid needs. Facilities and the EHS division work with a vendor to design and install a unit such as the one pictured above. The tank can be filled from a large cryogen transport vehicle, and both gas and liquid cryogen can be withdrawn from the system. These systems are most commonly used for liquid nitrogen and can be used to fill either a low pressure dewar or a cryogenic liquid cylinder. Often, the natural boil-off gas is also used (e.g., “house nitrogen”) after passing it through a heat exchanger to warm it to room temperature. In-depth on-the-job training is required for each individual filling station, as they are all unique installations. More information on cryogen filling stations and how to use them can be found in Work Process H.
Cryomagnets
Generally, cryomagnets are used for NMR and MRI applications, though they are also used in particle accelerators, some mass spectrometers, and for magnetic separations. The cryomagnet consists of a coil of wire, just like a standard electromagnet, but the wire is made of a material which is superconducting at very low (i.e., cryogenic) temperatures. Below a certain temperature threshold (usually ~10K), the wire begins to conduct current with insignificant resistance, allowing much higher currents, and thus the magnet can attain much higher field strengths, up to 25-30 Tesla. For comparison, a standard refrigerator or bulletin board magnet has a field strength of approximately 5/ths of one Tesla, and high-strength rare-earth magnets, such as neodymium magnets, have a field strength at their surface of roughly 1.25 Tesla. This document does not cover the hazards associated with high strength magnetic fields; information on the nature of cryomagnets is provided solely for context.
As the name implies, cryomagnets require cryogenic temperatures to operate. While a few high-temperature superconductors do exist, most superconductors require temperatures below about 10K (-263°C or -440°F) to exhibit superconducting properties; above that temperature, they conduct electricity like any other normal material, with normal resistance. This presents a risk because if the cryomagnet is allowed to warm to above ~10K it will lose its superconductivity and will immediately begin to produce significant heat as its resistance returns to normal. This is accompanied by a “magnet quench”, in which all of the cryogenic liquid that was being used to cool the magnet is rapidly boiled off by the heat produced by the coil. Since cryomagnets typically contain large volumes of both liquid helium and liquid nitrogen, this can cause severe and rapid oxygen depletion in the room, reducing oxygen levels to well below concentrations that can be fatal in a short period of time. These systems usually necessitate engineering controls such as oxygen monitoring, as described in Work Process D.
Magnet quenches are rare (at least one system at LBNL has gone for over 10 years without a single quench), but they are more likely to occur during maintenance of the system and filling of the cryogen reservoirs. Magnet quenches can also occur if the level of cryogen in the system drops too low to sustain superconducting temperatures, so it is important to follow the manufacturer’s instructions for the filling schedule of the cryogen reservoirs.
Only trained personnel should ever attempt to fill the reservoirs or perform maintenance on a cryomagnet system.
Cryostats
A cryostat is a system designed to maintain a cryogenic temperature in some experimental volume, device or sample chamber. There are multiple types of cryostats, but they all operate in roughly the same way: a cryogenic liquid is used, with the aid of heat exchangers, to cool the device of interest and keep it at a stable, cryogenic temperature.
The two most common types of cryostat are Continuous Flow Cryostats and Bath Cryostats. In a Continuous Flow Cryostat, a cryogenic liquid is flowed through a heat exchanger assembly and then allowed to warm, vaporize and vent into the atmosphere. The tube that carries the cryogen flow is typically vacuum shielded to keep the cryogen cold on its way to the heat exchanger, and is open to atmosphere past the heat exchanger such that the line is never pressurized. The cryogenic liquid is typically extracted from a cryogenic liquid cylinder.
A Bath Cryostat is the simplest type of cryostat and typically consists of a small reservoir of cryogenic liquid that is brought into thermal contact with the device of interest. The bath is allowed to vaporize into the atmosphere as it cools the device, and must be replenished either from a liquid flow from a cryogenic liquid cylinder, or by manually pouring more cryogenic liquid into the bath from a low pressure dewar.
Commercially available cryostat systems are available where the user need only connect a full cryogenic liquid cylinder to the device. When using a commercially available cryostat, users must follow all manufacturer’s instructions and safety precautions, in addition to the requirements in this document.
NOTE: A risk assessment of the oxygen deficiency hazard is still necessary, even with a commercially available cryostat system.
Cryogenic Storage and Shippers
Vacuum-jacketed vessels are available for both storage and shipping of cryogenically frozen samples. Vessels for storage and shipping differ somewhat, but both are constructed similarly to the low pressure dewars described in (i).
Cryogenic Storage Vessels are essentially a wide mouth version of low pressure dewars but also include a rack in which samples can be loaded and lowered into the cryogenic liquid. The vessel can be filled just like a low pressure dewar. The rack is designed to fit the specific storage vessel and can be easily lifted out. Users should wear cryogen gloves when inserting or removing samples. See Work Process H, section (i) for safe laboratory practices that apply when loading samples into a cryogen storage vessel and for removing closed containers from cryogenic liquid.
Cryogenic Dry/Vapor Shippers look much like their storage counterparts, but differ in one major way: these shipping containers only hold cryogenic liquid trapped within an absorbent material so that the cryogenic temperature is maintained inside the vessel, but there is no potential for a spill during transportation and shipping. Follow all manufacturer’s instructions for loading the shipper, adding cryogenic liquid if necessary, and packaging the vessel for transport or storage.
Anyone planning to self-transport a Cryogenic Dry/Vapor Shipper must follow the guidelines set out in Work Process H, section (ii). This includes:
Before purchasing or shipping a Cryogen Dry/Vapor Shipper, please contact the Cryogens SME for additional assistance and to have the vessel approved. See Work Process H section (ii) for more information on transport and shipping.
Before use, these vessels should be inspected for signs of damage, much like any low pressure dewar. In both cases, the vacuum jacket can fail and potentially allow cryogenic liquid to enter the vacuum space. Generally, the pressure relief valve is on the bottom of this type of vessel. After loading the vessel with cryogenic liquid, ice should not form on the outside of the aluminum casing – ice formation is a clear sign that the vacuum jacket has failed. If any signs of damage are evident (e.g., dents of the casing, scratches inside the silvered glass cryogen reservoir, corrosion, missing or damaged pressure relief valve, ice formation, etc.) the vessel should be taken out of service and marked as defective.
Only individuals who are trained, qualified and experienced in the repair of this type of vessel should ever attempt to repair a damaged cryogenic storage vessel or shipper.
An Overview of the ODH Calculator
The Oxygen Deficiency Hazard (ODH) calculator is a simple tool that allows rapid evaluation of the oxygen deficiency hazard of a room using conservative assumptions. It is well suited to simple cryogenic systems including the storage and filling of dewars, the use of freezers with cryogenic liquid backup systems, and the use of cryogenic liquids to cool cryomagnets. More complex systems will require a quantitative approach, as discussed in Step 6 below.
ODH Calculator Model
The Oxygen Deficiency Hazard calculator uses the Fermilab probabilistic methodology to determine the oxygen deficiency hazard (Fermilab ES&H Manual ). For each scenario, the value of %O2 is determined using the equation:
The probability of death upon exposure to this concentration of oxygen is calculated using the Fermilab methodology. Then finally, the probability of death for each scenario is multiplied by the probability of that scenario occurring, and the products for all scenarios are summed to give an overall probability of death resulting from cryogen use in this room. The ODH class is assigned using the values in Table C.2, below. Although this model uses a formula for the %O2 in the absence of ventilation for the probabilistic model, there is an implicit assumption of one air exchange per hour.
ODH Hazard Classification
Scenarios Considered in ODH Calculator Model
Liquid helium is the coldest of all the cryogens, with a boiling point of approximately 4K (-268.9°C or -452.1°F). This incredibly low temperature is cold enough to solidify air (the nitrogen and oxygen, not just the water) into a kind of ice. Because of this, it is far more common to accumulate solid obstructions in the valves of pressurized liquid helium cylinders than with nitrogen or argon. Users of liquid helium cylinders must exercise extreme care to prevent ice obstructions, which can cause liquid helium vessels to over-pressurize rapidly.
At the ALS, this exact situation occurred. A liquid helium cylinder was in use at the ALS, and a user failed to close one of the valves when finished with their operation. Nothing seemed amiss until a few days later, when another user went to withdraw liquid from the cylinder. This particular cylinder required that a long metal tube, a “stinger”, be inserted through the top of the cylinder all the way to the bottom of the cryogenic liquid reservoir in order to withdraw liquid. But the user found that the tube would not insert all the way; instead, it hit something hard well above the bottom of the reservoir. It turned out that air had entered the cylinder through the valve that was left open, had frozen solid on top of the liquid helium, and formed an impenetrable plug. Had the situation not been discovered and remedied, the cylinder may have exploded as the helium trapped below the plug slowly vaporized and built up pressure in the confined space.
Unlike nitrogen and argon, which are denser as gases than air, helium as a gas is far less dense than air. With liquid nitrogen and liquid argon, the largest danger of asphyxiation is close to the ground, especially in recessed areas. However, with liquid helium the largest danger of asphyxiation is at ceiling level, where the helium gas will accumulate and displace oxygen most rapidly. Therefore, when working with cryogenic helium, users must be aware of what is above them. People on catwalks or ladders will be more quickly affected by a release of helium gas than someone on the ground.
Pressurized liquid helium cylinders are rarely operated at high pressures like liquid nitrogen or liquid argon which come in cylinders with pressures up to 350psig. Instead, most liquid helium cylinders are operated at less than 20psig. Cryogenic liquid cylinders used for helium sometimes have more complex insulation systems to minimize loss rates, which can be quite high for liquid helium. Cryogenic liquid cylinders intended for use with liquid nitrogen or liquid argon are likely to be completely unsuitable for containing liquid helium.
Always check that the cryogenic liquid cylinder is clearly marked for use with helium before attempting to fill it with liquid helium. Follow all manufacturer’s instructions for the cylinder carefully to prevent ice obstructions and over-pressurization of the cylinder. Valve sequencing may be far more complex, even for routine operations, and is incredibly important, as demonstrated by the incident at ALS.
Example of a Relatively Simple Valve Sequence from Air Products:
In addition to being one of the coldest cryogenic liquids with a boiling point of only 20K, hydrogen is an extremely flammable material. Hydrogen gas is explosive in air from concentrations as low as 4% by volume. Even if an asphyxiation hazard does not exist from boil-off of hydrogen gas, the atmosphere around the source may still be flammable and/or explosive. The initiation energy for this reaction is also incredibly low, meaning that even a small spark, a static electricity discharge, or a nearby hot material may initiate a hydrogen gas fire or explosion. All equipment used for or near liquid hydrogen operations must therefore be electrically grounded and bonded to reduce the risk of explosion. A hydrogen leak which catches fire will produce a very pale blue, almost invisible flame which is easy to miss and personnel may unknowingly walk into or place a hand into a hydrogen flame.
Because hydrogen is so flammable and readily explosive, extreme care must be taken so that it never comes into contact with air. Liquid hydrogen cylinders should never be used for other cryogenic liquids, and cylinders intended for other cryogenic liquids should never be used for liquid hydrogen. All lines used to transfer hydrogen gas or liquid must be thoroughly purged of air by evacuating the lines and backfilling with inert gas at least three times. Additionally, any pressure relief valves on a liquid hydrogen cylinder must be routed to minimize the risk of creating a flammable or explosive mixture with air. Transfer lines carrying liquid hydrogen are also prone to condensing air and forming oxygen enriched liquid or atmosphere, which only increases the risks of fire or explosion when working with liquid hydrogen. Vacuum insulated transfer lines are thus a necessity with liquid hydrogen.
Unlike nitrogen and argon, which are denser as gases than air, hydrogen as a gas is far less dense than air. With liquid nitrogen and liquid argon, the largest concentrations of released cryogen will be close to the ground, especially in recessed areas. However, with liquid hydrogen the vented gas will accumulate at ceiling level, at the highest point. Hydrogen concentrations can be far greater in vaulted areas of the ceiling or in the open area above a drop ceiling, where room ventilation systems may not flush it out as effectively. These types of features pose a large asphyxiation and fire/explosion hazard.
The inherent dangers of working with liquid hydrogen cannot be overstated. A thorough review by EHS personnel will be needed for any proposed work with cryogenic liquid hydrogen, and all liquid hydrogen systems must comply with Cal/OSHA’s General Industry Safety Orders, Group 20, Article 138.
Although oxygen is not flammable in itself, it is a strong oxidizer and can cause flammable and combustible materials to catch fire and burn. As discussed throughout this chapter, our atmosphere typically contains about 21% oxygen by volume. This is plenty of oxidizer to burn a wide range of flammable and combustible materials. Liquid oxygen is not only 100% oxygen by volume, but that oxygen is far more concentrated as a liquid than as a gas, since liquid oxygen expands by 860 times when allowed to warm to room temperature. A single drop of liquid oxygen has as many oxygen molecules, and thus as much oxidizing power, as approximately half a liter of air. It should not be surprising, then, that liquid oxygen is capable of causing fires in materials that aren’t normally considered flammable by the layperson, while materials which are known to burn in air will burn far more vigorously in atmospheres with increased oxygen concentration. Some materials may even ignite spontaneously on contact with liquid oxygen or high gaseous oxygen concentrations.
Hair, clothing, oil, grease, kerosene, tar, asphalt, and many plastics and rubbers will all burn readily in oxygen rich environments. In particular, cloth and clothing can trap oxygen gas in the porous weave of the fibers and remain incredibly prone to ignition long after the source of oxygen has been removed. Clothing that has been exposed to liquid oxygen will burn incredibly hot and fast if ignited, and will ignite more easily. All sources of ignition and incompatible materials must be kept away from liquid oxygen operations.
Vessels that contain liquid oxygen must be cleaned to very strict standards to ensure that no hydrocarbon or other incompatible contaminant is present. Oxidation of incompatible materials by liquid oxygen produces significant heat which causes the liquid oxygen to vaporize and expand quickly, potentially leading to the rupture of its container. The construction of a vessel to contain liquid oxygen must also avoid the use of any material which may oxidize or burn on contact with liquid oxygen. This makes liquid oxygen vessels unique in their construction. Liquid oxygen should never be added to any vessel of any type unless it is specifically constructed for use with LOx and has been cleaned according to strict protocols to ensure the complete removal of incompatible contamination.
Unlike every other cryogenic liquid, LOx does not pose an asphyxiation risk. However, at high enough concentrations oxygen may damage the lungs, airways and eyes.
A thorough review by EHS personnel will be required for any proposed work with cryogenic liquid oxygen, and all liquid oxygen systems must comply with Cal/OSHA’s General Industry Safety Orders, Group 20, Article 139.
The intent of this section is to provide a quick way of assessing the potential for creating an oxygen deficient environment when using cryogens in indoor settings. Normal air contains nominally 20.9% oxygen. Cryogen, when released indoors in non-ventilated rooms, has the potential of displacing oxygen and thereby creating an oxygen deficient atmosphere (i.e., less than 19.5% oxygen by volume). While this section focuses on liquid nitrogen, these calculations can be applied to any cryogen by substituting the appropriate factor for the expansion of a volume of cryogenic liquid to gas upon warming to room temperature. A sampling of these factors can be found in Work Process A, Table A.1.
Calculation of Oxygen Depletion Due to Liquid Nitrogen Losses
Four cases are considered here:
The British Compressed Gases Association (BCGA) recommends that, for the purpose of risk assessment, the worst case possibility (iv) must be considered.
General Oxygen Concentration Calculation
The oxygen concentration, in a room as a percentage may be calculated:
Eq. 0
Where:
Voxygen is the volume of oxygen in the room in m3, calculated as in (ii), (iii), or (iv) below
Vroom is the total volume of the room, in m3
Normal evaporative losses
Over sufficiently long periods, the percentage of oxygen remaining in a room due to normal evaporation losses from a vessel is approximately:
Eq. 1.1
Where:
0.209 represents the normal concentration of oxygen in air (20.9%)
is the increase in percent nitrogen concentration from the evaporation of the dewar
Given the evaporation loss rate for a vessel, the increase in nitrogen concentration can be calculated:
Eq. 1.2
Where:
L is the evaporation rate of the dewar in m3 per hour
Vroom is the volume of the room
N is the number of air exchanges per hour from the room’s ventilation
Manufacturers usually quote the evaporation rate for their vessels as a volume of liquid nitrogen lost per day in the specifications of the dewar model (usually this information can be found on the manufacturer’s website), which must be converted to a volume of gaseous nitrogen produced per hour. Additionally, allowance should be made, by doubling these figures, for the deterioration of insulation performance over the lifetime of the vessel. Thus the evaporation loss rate that will be used is calculated:
Eq. 1.3
Where:
2 allows for an increased loss rate due to the deterioration of insulation
696 represents the gas factor for nitrogen (1 liter of liquid nitrogen expands to 696 liters of gas)
accounts for the conversion from L to m3
And 24 converts from a loss rate per day to a loss rate per hour.
EXAMPLE
For example, a small microscope room measures 10ft x 12.5ft by 8ft tall, and contains one 15-liter storage dewar, whose evaporative loss is quoted by the manufacturer as 0.8L liquid nitrogen per day. This room has no fume hoods or other sources of increased ventilation, and thus has only 0.4 air exchanges per hour. Using equation 1.3, the evaporation loss rate is:
Given that 1 cubic foot is equal to 0. cubic meters, the volume of the room can be calculated:
And the increase in nitrogen concentration, using equation 1.2, is:
Therefore, the resulting oxygen concentration, using equation 1.1, is:
In this case, the normal evaporation losses have an insignificant effect on the oxygen content of the room. However, where the increase in Nitrogen concentration, is 7% or higher, the resulting oxygen concentration will drop below 19.5%, and extra ventilation and/or oxygen monitoring will be required.
Filling losses
When a vessel is filled, some loss always occurs as it is cooled to liquid-nitrogen temperature. The British Compressed Gases Association, BCGA, recommends that a loss of 10% of the vessel’s capacity should be assumed in order to assess the risk from filling losses. We can calculate the volume of oxygen remaining in the room after filling:
Eq. 2.1
Where:
is in m3
0.209 represents the normal concentration of oxygen in air (20.9%)
0.1 represents the loss of 10% of the vessel’s capacity
Vvessel is the vessel’s capacity in liters
696 represents the gas factor for nitrogen (1 liter of liquid nitrogen expands to 696 liters of gas)
The factor of is used to convert from the vessel volume from L to m3
EXAMPLE
A small room is used to house the filling station for other laboratories in the area. This room measures 10ft by 14ft by 10ft tall. A researcher wishes to fill a 34L storage dewar from the fill station.
Converting the room measurements to a volume in m3, we obtain:
Using equation 2.1, followed by equation 0, we calculate:
In this case, the oxygen level is very close to dipping below 19.5%. The researcher should consult their supervisor to determine if a full Oxygen Deficiency Hazard analysis should be conducted with the help of EHS.
Spillage
For the spillage of the entire contents of a vessel:
Eq. 3.1
Again, 696 is the expansion factor for nitrogen from liquid to gas and dividing by accounts for the conversion from L to m3.
We then use equation 0 to calculate the oxygen concentration in the room.
EXAMPLE
If a researcher working in the small microscope room described above (which measures 10ft x 12.5ft x 8ft tall) were to spill the 15-liter dewar, we calculate the remaining oxygen concentration using equation 3.1 followed by equation 0:
This spillage would significantly deplete the oxygen concentration, leading to an extremely dangerous situation for the researcher. The researcher should contact their supervisor and obtain help from EHS to conduct an Oxygen Deficiency Hazard analysis on this microscope room before performing any work with cryogens there.
Filling of a vessel followed by the spillage of its entire contents
Eq. 4.1
Where:
1.1 represents 10% filling loss + 100% loss of the vessel’s contents by spillage
This is the worst case that should be considered in the risk assessment—both (ii) and (iii) are taken into account.
EXAMPLE
Let us consider a 10-liter dewar being filled at the aforementioned filling station, followed immediately by the spillage of its entire contents. Using equation 4.1 followed by equation 0, we calculate:
This calculation shows that even filling a 10L dewar in such a small space can be dangerous if the dewar were to spill during the filling operation.
If the risk assessment shows that oxygen depletion will occur (oxygen level below 19.5%) in any of these situations, EHS must perform an Oxygen Deficiency Hazard risk analysis. If the risk analysis shows an Oxygen Deficiency Hazard rating of 1 or greater, alternative arrangements must be considered or oxygen monitoring must be installed. Alternative arrangements may include:
1.-
Which dewar should I use?
2.- Can you teach me how to transfer?
3.- What's that awful smell?
4.- Why are you bothering me?
5.- I feel like you guys are watching me
all the time?
What gives?
6-. Why can't I take a dewar at 9 am
weekdays?
7.- Why does my cryostat keep plugging?
8.- Why can't I keep a dewar in my lab?
9.- Why must I return empty gas cylinders
when I take
a full one?
10.- What's the best way to request liquid
helium?
cylinder gasses?
11.- Why is Cryogenic Services' door
closed during
business hours?
12-. Where do I get liquid nitrogen?
13.- What's the best way to get cylinder
gasses?
14.- What are your rates?
Questions asked
from people not associated
with the University of Florida;
1.-
What Helium Liquefier do
you have?
2.- How much helium do you produce? per
year?, per month?,
per day?, per hour?
3.- How much helium gas do you recover?
4.- How do you measure impurities?
5.- Do you recover helium from remote labs?
6.-How many people use helium at UF?
1.- Which dewar should I use?
A: Most dewars are shared. If you are not speciffically assigned a dewar, you should use the one with the lowest liquid level from which you can get a complete transfer. Assigned dewars are labelled in the NPB or are noted on the dewar room entrance door in CLB or on the whiteboard in the hallway of Williamson for the Microkelvin Lab and Williamson users. An from Cryogenic Services is the most definitive.2.- Can you teach me how to transfer?
A: The primary responsibility for all training in individual labs is with the PI for that lab. However, we are more than willing to train lab personel in the proper methods of helium transfer.3.- What's that awful smell?
A: In each lab is a water drain. After long periods of no use, they dry out and allow sewer gasses to enter the lab. Pour at least one gallon of water into the drain and the odor should diminish rapidly. It will smell like a natural gas leak. If the odor does not go away and you think it may be an actual gas leak, leave the area and call 2-.4.- Why are you bothering me?
A: We are not bothering you. We are here to help you. If you play by our rules, you will be happier. We will be happier and your PI will be happier because his bills will be lower.5.- I feel like you guys are watching me all the time? What gives?
A: In a sense, we are watching you all the time. We have a data gathering system called the Cryonet which allows us to monitor all aspects of the liquid helium and recovery resources, including monitors in your lab. If we notice any anomallies we dispatch immediately to prevent small problems from becoming dangerous or large expensive problems. In the Cryogenic Services area, we have several cameras for monitoring the activity within, including the dewar storage room, so that we can assure visitors' safety and dewar assignment compliance.6-. Why can't I take a dewar at 9 am weekdays?
Every morning at 9 am, the system of computers and data acquisition boxes, know as the Cryonet, poll every helium dewar and gasmeter for a daily inventory and for the previous days' helium usages. If a dewar is not plugged into the network, its data will be missing for that day and disrupts the ability to accurately take an inventory. The daily inventory is a very important method to asses the sysytems' worthyness and to keep the cost of helium low.7.- How come your dirty helium makes my cryostat plug up?
A: Most plugs are caused by sloppy procedures in the lab, however, we made a supply of transfer tube filters that each lab can have free of charge to reduce the chances that "dirty" helium can cause a plug. The root cause of dirty helium, is sloppy procedures in the lab that contaminate the transport dewars.8.- Why can't I keep a dewar in my lab?
A: To reduce the cost of having an in house helium system, we share transport dewars to reduce the total number of dewars we need and to maximize the efficient usage of the ones in use. If a dewar is stored in the lab when not in use, it costs everyone more money and inconvienences the other labs who need helium.9.- Why must I return empty gas cylinders when I take a full one?
A: The rental fees on cylinders can be more than the cost of the product in the cylinder. We provide cylinders and the gas in them at no cost to the labs. So you have no reason to complain.10.- What's the best way to request liquid helium?
A: On the web here, , on the clipboard sign out sheets, , in-person - in that order.11.- Why is Cryogenic Services' door closed during business hours?
A: Since there are only two staff members there are frequently times that we are both needed outside the Cryogenic Services area, for helium deliveries and maintenence demands. For everyone's safety, no one is allowed into the Cryogenic Services area without one of us here.12-. Where do I get liquid nitrogen?
A: To fill lab supply dewars, there is a fill port on the loading dock of the NPB, and in the hallway of Williamson. For academic liquid nitrogen or for small infrequent needs a 160 liter storage dewar is located in the Helium dewar storage room B123. All liquid nitrogen fills should be logged on the computer in the fill station area. You should be trained by your PI or us before ever attempting to get liquid nitrogen on your own.13.- What's the best way to get cylinder gasses?
A: There is a request form in B123 for cylinder gasses. Or you can ask one of us in person. Helium cylinders are stocked in B123. Nitrogen and Argon and most other common gases can be ordered within a day or two. If you need Special and/or high purity gasses, you should plan ahead, allowing for up to a month to receive them.14.- What are your rates?
A: rates.htmTop
Questions asked from people not associated with the University of Florida;
1.- What Helium Liquefier do you have?
The company is the world’s best Liquid Dewar Cylinder supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.
A: LindeBOC AS with two RS compressors installed in . Prior to that we had a Process Systems International -AS with a single RS compressor installed in . Prior to that we had an Air Products Helifier installed in and before that an ADL Collins Liquefier installed in .2.- How much helium do you produce? per year?, per month?, per day?, per hour?
A: We don't keep track of production because there is no easy way to get an accurate rate. What we track is the amounts used by the labs. Production can be 20-40% higher. We have a web area devoted to usage. See reports, annual graph, monthly graph, and our liquefier produces about 50 liters per hour while running 2-5 days per week.3.- How much helium gas do you recover?
A: System wide, Roughly 90%. The majority of labs recover 95% or better. Because of the helium shortage we have all labs on helium recovery now.4.- How do you measure impurities?
A: We use three GOW-MAC 20-260 Air in Helium purity monitors, and a Kahn Hygrometer. The devices are the best money you will ever spend on a helium recover system. Both are connected to the cryonet data network to look for trends. Trends are way more informative than the instantaneous ones.5.- Do you recover helium from remote labs?
A: Yes, we have recovery extended to 7 remote buildings up to one mile away by using custom built UF designed, low pressure recovery systems.6.- How many people use helium at UF?
A: We serve Physics, Chemistry, The McKnight Brain Institute, Material Sciences, Astronomy and Geology with about 42 seperate individual labs with one to many people in each one.7.-